Application of gas chromatographic technique for investigation of the formation of by products in drinking water disinfection

The use of chlorine for disinfection and/or oxidation at drinking water treatment plants favors the formation of halogenated organic by-products (HOB), many of them carcinogenic. The purpose of this research was to validate an analytical method for the simultaneous quantification of 12 HOB from disinfection by gas chromatograph with electrons capture detector (GC-ECD). The method provided linearity (r>0.998), repeatability lower than 0.15%, limits of detection from 1 to 6 Î1/4g.L-1 and of quantification from 3 to 21 Î1/4g.L-1, precision (<10%), accuracy (93-120%) and recovery (87-117%). The results indicate that the method can be employed to investigate the formation of HOB in water, yielding analytically reliable results

halogenated organic compounds; gas chromatograph; other disinfection by-products; disinfection by-products; trihalometanes