Acessibilidade / Reportar erro

Ascarel determination in insulating oil of transformers

The contamination level of silicon oil used as insulation liquid in high-voltage transformers by ascarel (PCBs) is above those permitted by the Brazilian law. Thus new techniques able to detect ascarel, with low operational costs, are very attractive. The present work proposes an analysis of the contamination levels of silicon oil using the following techniques: naphthalene anion radical reaction for ascarel dechlorination; and potentiometry with an ion-selective electrode for chloride ion determination. The data obtained with the proposed methodology agree well with those from the official methodology, (method IEC 61619).

ascarel; PCBs; dechlorination


Sociedade Brasileira de Química Secretaria Executiva, Av. Prof. Lineu Prestes, 748 - bloco 3 - Superior, 05508-000 São Paulo SP - Brazil, C.P. 26.037 - 05599-970, Tel.: +55 11 3032.2299, Fax: +55 11 3814.3602 - São Paulo - SP - Brazil
E-mail: quimicanova@sbq.org.br