Acessibilidade / Reportar erro

Air contamination levels in operating rooms during surgery of total hip and total knee arthroplasty, hemiarthroplasty and osteosynthesis in the surgical center of a Brazilian hospital

INTRODUCTION: The air contamination levels during orthopedic surgeries were evaluated. METHODS: The air of operating rooms (ORs) was examined through exposure to microbiological plates placed near the surgical table for an hour. RESULTS: values above that recommended (369 CFU/m³) for conventional ORs and ORs with ultraclean air were determined. Contamination was predominantly by Staphylococcus sp (86.9%). In all surgeries a high number of people were present inside the ORs and the doors were opened frequently. CONCLUSIONS: The contamination levels are above the values accepted by regulatory agencies, representing risk for patients.

Operating theatre; Airborne infection


Sociedade Brasileira de Medicina Tropical - SBMT Sociedade Brasileira de Medicina Tropical - SBMT, Núcleo de Medicina Tropical – UnB, Sala 43C – 70904-970, E-mails: rsbmt@uftm.edu.br | artes.rsbmt@gmail.com | sbmt@sbmt.org.br , WhatsApp: SBMT (61) 9.9192-6496, WhatsApp: RSBMT (34) 9.9996-5807 - Brasília - DF - Brazil
E-mail: rsbmt@uftm.edu.br